JE-H(St)HRH

Fire Alarm Cable JE-H(St)HRH is suitable for all locations where it is necessary to avoid loss of persons and goods in case of fire. Electrostatic shielding prevents powerful interference pulses. Suitable for fixed installations in all places where there is a special requirement to protect people’s lives and property in the event of a fire, e.g. industrial parks, public buildings, hotels, airports, metro networks, hospitals.

Standard and Approvals

VDE 0815, DIN 4102, DIN EN 61034/IEC 61034,
DIN EN 50267/IEC 60754
Flame Retardant according to VDE 0482-266-2-4
/IEC 60332-3-24 (Cat. C)

Cable Structure:

Conductor: Bare copper
Insulation: LSZH
Jacket: LSZH
Screen: Al-Foil
Drain Wire: Solid tinned copper drain wire 0.8mm

Technical data:

Halogen-free, 
Flame retardant, non-flammable
Temperature range -30°C to +70°C 

Self-extinguishing and fire resistant

Flame does not propagate and is therefore fire resistant

 Low smoke density, low damage to escape and fire protection

FE 180: insulation integrity 180 min.
Tested in accordance with DIN VDE 0472 part 814 IEC60331

E 30: Ensure that the cable functions properly for a minimum of 30 minutes.

This 30-minute functional guarantee feature ensures that people and animals can be saved in the event of a building fire.

It ensures that fire alarm and warning systems, security and backup lighting, and passenger elevators with evacuation routes are operational within 30 minutes.

NO. OF PAIRSNOMINAL CROSS SECTIONAL AREA mm*NOMINAL OVERALL DIAMETER mmNOMINAL WEIGHT kg/km
20.87.576
40.89.3130
80.811.4232
120.813.5318
160.815430
200.816.5514
320.819.5730
400.822.5962
520.825.21200

Request A Free Quote