NYM Cable

NYM Power cable is suitable for industrial and domestic applications. It can be used in dry and wet open areas and can also be installed in lime plaster, walls and under concrete, but cannot be laid in tight concrete. It can also be used outdoors in conditions where direct sunlight is avoided.

Standard and Approvals

DIN VDE 0281-1, UNE 21031-4, HD 21.4S2, IEC 60227-4,
DIN VDE 0295, EN 60228, IEC 227- 4 MOD, VDE 0250-204
Flame Retardant according to IEC/EN 60332-1-2

Cable Structure:

Conductor: Solid or stranded, plain copper conductor
Insulation: PVC
Jacket: PVC

Technical data:

– Working voltage: 300/500 volts
– Test voltage: 2000 volts
– Minimum bending radius: 4 x Ø
– Flexing temperature: +5º C to +70º C
– Fixed installation temperature: – 40º C to +70º C
– Flame retardant: IEC 60332.1
– Insulation resistance: >20 MΩ x km

AWGNO. OF CORES X NOMINAL CROSS SECTIONAL AREA # X MM2NOMINAL THICKNESS OF INSULATION MMNOMINAL THICKNESS OF SHEATH MMNOMINAL OVERALL DIAMETER MMNOMINAL COPPER WEIGHT KG/KMNOMINAL WEIGHT KG/KM
16(solid)1X1.50.61.45.414.440
16(solid)2X1.50.61.48.729170
16(solid)3X1.50.61.49.143135
16(solid)4X1.50.61.49.858160
16(solid)5X1.50.61.410.372190
16(solid)7X1.50.61.411.5101235
16(solid)10X1.50.61.413.8144330
16(solid)12X1.50.61.414.4173405
14(solid)1 X2.50.71.462470
14(solid)3X2.50.71.410.472190
14(solid)4X2.50.71.411.396230
14(solid)5X2.50.71.412120270
14(solid)7X2.50.71.613.2168342
12(solid)1X40.81.66.63880
12(solid)3X40.81.612115258
12(solid)4X40.81.613154330
12(solid)5X40.81.614.5192410
10(solid)1X60.81.67.258105
10(solid)3X60.81.613173320
10(solid)4X60.81.615.1230460
10(solid)5X60.81.616.1288540
8{solid)1X101.01.68.496155
8(solid)4X101.01.617.6384680
8(solid)5X101.01.619.2480850
6(7/14)1X161.21.89.9154230
6(7/14)4X161.21.821.36141048
6(7/14)5X161.21.823.47681280
4(7/12)1x251.42.012240325
4(7/12)4X251.42.025.89601649
4(7/12)5X251.42.028.712001970
2(7/10)4X351.42.028.513442000