JE-H(St)H fire alarm cable, Flame retardant, halogen free, electrostatically shielded, installation cable for telecommunications. Electrostatic shielding prevents strong interference pulses. Suitable for fixed installations in all places where the protection of human life and
In all places where the protection of human life and property is particularly important in case of fire, e.g. industrial parks, public buildings, hotels, airports, metro networks, hospitals.
VDE 0815, DIN 4102, DIN EN 61034/IEC 61034,
DIN EN 50267/IEC 60754
Flame Retardant according to VDE 0482-266-2-4
/IEC 60332-3-24 (Cat. C)
Halogen-free,
Flame retardant, non-flammable
Temperature range -30°C to +70°C
Self-extinguishing and fire resistant
Flame does not propagate and is therefore fire resistant
Low smoke density, low damage to escape and fire protection
FE 180: insulation integrity 180 min.
Tested in accordance with DIN VDE 0472 part 814 IEC60331
E 30: Ensure that the cable functions properly for a minimum of 30 minutes.
This 30-minute functional guarantee feature ensures that people and animals can be saved in the event of a building fire.
It ensures that fire alarm and warning systems, security and backup lighting, and passenger elevators with evacuation routes are operational within 30 minutes.
NO. OF PAIRS | NOMINAL CROSS SECTIONAL AREA mm* | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km |
---|---|---|---|
2 | 0.8 | 7.5 | 76 |
4 | 0.8 | 9.3 | 130 |
8 | 0.8 | 11.4 | 232 |
12 | 0.8 | 13.5 | 318 |
16 | 0.8 | 15 | 430 |
20 | 0.8 | 16.5 | 514 |
32 | 0.8 | 19.5 | 730 |
40 | 0.8 | 22.5 | 962 |
52 | 0.8 | 25.2 | 1200 |
Or contact us to see our certificates
Send us a message if you have any questions or request a quote. Our experts will give you a reply within 24 hours and help you select the right valve you want.
No. 2 Changsheng Road, Zhitang Town, Changshu City, Suzhou City, Jiangsu Province, China